HT INDUSTRIAL AUTOMATION LIMITED

 
PROUDCTS:Home > Proudcts > DCS and Parts
ARS55M


YOKOGAWA
ARS55M 32 Solid State Outputs (SSR Plug-In Type, Pressure Clamp Terminals)


YOKOGAWA Relay Boards (for FIO):

ARM15A, ARM55D, ARM55W, ARM55T, ARM55C, ARS15B, ARS15M, ARS55M


GENERAL

This document describes the specifications of relay board used in FIO subsystem of CENTUM VP. Relay input/ output boards are connected in between digital input/output modules (for FIO) and field devices. Relay input boards receive contact signals or voltage input signals of field devices. Relay output boards receive output signals of the digital output module and amplify by the relay, and then output to field devices.   These relay boards support dual- redundant digital input/output modules (for FIO).


MODELS
 AND SUFFIX CODES

Description

Model

ARS55M

32 Solid State Outputs (SSR Plug-In Type, Pressure Clamp Terminals)

Sufx Codes

-1

For 100 V AC output module (32-point type)

-2

For 220 V AC output module (32-point type)

-3

For 5-60 V DC output module (32-point type)

1

DIN Rail Mountable

0

Basic Type


Ordering Examples:

ARS55M-110

ARS55M-210

ARS55M-310


Solid
 State Relay Boards (Voltage Output)

Models

ARS55M-1 (100 V AC)

ARS55M-2 (220 V AC)

ARS55M-3 (5 - 60 V DC)

Usage

Solid State Relay TRIAC Output, Transistor output (Single / Dual-redundant)

Contact Points

32-point

Terminals for Field Device

Connection

Pressure clamp terminals

Cable specifications: see the table of terminal treatment for the pressure clamp terminal signal line and power line.

Modules

ADV551 (DO: 32-point) + ATD5A (Terminal block) ADV561 (DO: 64-point) (*1)

Signal Cables

AKB331 (for  2-point) AKB337 (for 64-point)

Output Voltage/Current Range

(*2)

24 to 140 V AC

30 mA to 2.5 A

(Ambient temperature is under

20 °C)

30 mA to 2 A (at 20 to 35 °C)

30 mA to 1.5 A (at 35 to 40 °C)

30 mA to 1.3 A (at 40 to 50 °C)

Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C.

24 to 250 V AC

30 mA to 2.5 A

(Ambient temperature is under

20 °C)

30 mA to 2 A (at 20 to 35 °C)

30 mA to 1.5 A (at 35 to 40 °C)

30 mA to 1.3 A (at 40 to 50 °C)

Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C.

5 to 60 V DC

20 mA to 2.5 A

(Ambient temperature is under 20 °C)

20 mA to 2 A (at 20 to 35 °C)

20 mA to 1.3 A (at 35 to 50 °C)

Inductive load must be 1.5 A or less.

Power Supply Voltage and Current Consumption of Internal Circuit

(require external power supply)

24 V DC Max. 0.9 A

Power Supply for Field Device

-

Insulation Resistance

At least 10 M (500 V DC)

Withstanding Voltage

Between 24 V power terminals and field device terminals: 2 kV

Ambient Temperature and

Humidity

0 to 50 °C, 10 to 90 %RH

Standards

Safety Standard [CSA], EMC standards [CE Marking], [C-Tick Marking] , [KC Marking]

Size

W: 436 mm x H: 125.4 mm

Weight

3.0 kg

#
copyright 2009-2021  HT INDUSTRIAL AUTOMATION LIMITED